TECHNICAL PARTICULARS OF DISTRIBUTION TRANSFORMERS 11/0.433kV
| Sr.NO | KVA | (HV) Primary Voltage | (LV) secondary Voltage | No Load (Watts) | Load Loss (Watts) | Impedance(%) | Dimension Lx B x H(mm) |
| 1 | 250 | 450 | 3200 | 4.5 | 1620 x1170 x1620 | ||
| 2 | 315 | 500 | 4000 | 4.5 | 1620 x 1170 x1620 | ||
| 3 | 400 | 600 | 4800 | 4.5 | 1440x1170 x1800 | ||
| 4 | 500 | 770 | 5500 | 4.5 | 1440 x 1350 x 1800 | ||
| 5 | 630 | 850 | 6000 | 4.5 | 1540 x 1440 x 1890 | ||
| 6 | 750 | 900 | 7000 | 4.5 | 1890 x 1440 x 2250 | ||
| 7 | 800 | 11KV | 0.433KV | 980 | 7400 | 5 | 1980 x 1800 x 2340 |
| 8 | 1000 | 1000 | 10000 | 5 | 1980 x 2250 x 2340 | ||
| 9 | 1250 | 1200 | 11800 | 5 | 1980 x 2250 x 2340 | ||
| 10 | 1500 | 1450 | 15000 | 6.25 | 2340 x 2520 x 2880 | ||
| 11 | 1600 | 1550 | 16000 | 6.25 | 2340 x 2520 x 2880 | ||
| 12 | 2000 | 1700 | 18000 | 6.25 | 2430 x 2880 x 2970 | ||
| 13 | 2500 | 2000 | 22000 | 6.25 | 2500 x 3200 x 3050 | ||
| Note :- | |||||||
| The above quoted losses and impedance are subjected to tolerance as per IS -2026 | |||||||
| 2) Design & Manufacture of our products are subject to constant improvement, The products supplied may differ in some detail from the specifications, & mentioned above | |||||||